Antifreeze measures for closed cooling tower

Oct 26, 2024

When the temperature is below zero, the antifreeze problem of closed cooling tower operation becomes more and more serious. If it is not solved well, the heat exchange tube or other parts of the cooling tower may be frozen. According to different process characteristics, some closed cooling towers run all day in winter, some run for part of the time, and some are basically not used. But antifreeze problems should be considered.

 

1. Antifreeze measures for non-operation in winter
If the closed cooling tower does not need to be operated in winter, the spray water and internal circulating water must be drained when it is shut down.

 

2. Antifreeze measures for part of the operation time
The antifreeze of closed cooling towers has two parts: the spray water system and the internal circulating water system. The antifreeze problem of the spray water system usually adds an electric heater in the water accumulation tray, which is generally turned on when the spray water is lower than 5℃ and stopped when it is above 8℃. The temperature probe transmits the signal to the control cabinet to automatically control the start and stop of the electric heater. The power selection of the electric heater is determined by the circulating water volume and the outside temperature. The antifreeze of the internal circulating water system can be added with ethylene glycol solution or electric heating equipment.

 

3. Antifreeze measures for year-round operation
If the closed cooling tower is equipped with an electronic control system, the load change of the main system may cause changes in the number of cooling towers in operation, so antifreeze issues also need to be considered.

https://www.kejucooling.com/

 

You Might Also Like